EWK-A

  • ADIABATIC COOLERS
  • AXIAL VENTILATION

Close circuit adiabatic water coolers

  • Casing made of fiberglass-reinforced polyester
  • Cu-Al heat exchanger
  • Possibility of installation of AC, AC+ or EC high efficiency (IE4+) Fans
  • Water treatments not necessary
  • Aerosol free
  • Autonomous management of energy saving, with two working options
  • Frequency converter included
  • High efficiency Evaporative panel, easy to remove

Technical Features

Model *Dissipation
kw
Empty weight
kg
Service
weight kg
Fan Power
kw
Long
mm
Wide
mm
High
mm
Dim. Drawing Plane DWG
EWK-A 730/3 262,5 1127 2040 2 x 6,5 3901 2080 2550 seleccionar seleccionar
EWK-A 730/4 297,8 1277 2190 2 x 6,5 3901 2080 2550 seleccionar seleccionar
EWK-A 1040/3 391,5 2192 2559 3 x 6,5 5511 2080 2550 seleccionar seleccionar
EWK-A 1040/4 448,7 2492 2917 3 x 6,5 5511 2080 2550 seleccionar seleccionar
EWK-A 1350/3 524,5 2922 3419 4 x 6,5 7116 2080 2550 seleccionar seleccionar
EWK-A 1350/4 596,2 3322 3897 4 x 6,5 7116 2080 2550 seleccionar seleccionar
EWK-A 1670/3 654,8 3652 4280 5 x 6,5 8716 2080 2550 seleccionar seleccionar
EWK-A 1670/4 744,8 4153 4878 5 x 6,5 8716 2080 2550 seleccionar seleccionar
EWK-A 1980/3 782,3 4383 5117 6 x 6,5 10316 2080 2550 seleccionar seleccionar
EWK-A 1980/4 896,7 4983 5833 6 x 6,5 10316 2080 2550 seleccionar seleccionar
EWK-A 2290/3 915,3 5113 5977 7 x 6,5 11916 2080 2550 seleccionar seleccionar
EWK-A 2290/4 1045,3 5814 6814 7 x 6,5 11916 2080 2550 seleccionar seleccionar

* Heat rejection at the following conditions: Tentr: 35,0 ºC, Tsal: 30,0 ºC, TBh: 24,0 ºC

Working Principles

Especially designed to refrigerate water with minimum costs, thanks to the combination of two working options, dry and wet. The ‘dry’ operation cools the fluid that circulates through the machine with air at ambient temperature. The ‘wet’ operation consists in modifying the humidity conditions of the air, thus obtaining fresher air to use to cool the process fluid more efficiently, and having a great energy saving.

Additional equipment

  • Fin coil protection coat
  • Master control
  • Temperature sensor control
your energy source

© ENERGETUS