EWK Modular

  • AXIAL VENTILATION
  • OPEN CIRCUIT

Open circuit Cooling Tower for big water flows, pre-assembled from the factory.

  • Broad Range: From 500 to 10.000 m3/h)
  • Modular design in FRP
  • Corrosion free
  • Standard Fill materials in Polypropylene with anti-legionella treatment (SANIPACKING®)
  • Industrial applications
  • Easy maintenance
  • Materials highly resistant to all aggressive conditions, as well as to extreme temperatures
  • Pre-assembled at the factory
  • Three different options:
    • A) WITH complete basin and inlet Louvers
    • B) WITHOUT basin but WITH  Inlet Louvers
    • C) WITHOUT basin and WITHOUT Louvers

Technical Features

Model *Dissipation
kw
Empty weight
kg
Service weight
kg
Fan Power
kw
Long
mm
Wide
mm
HIgh
mm
Dim. Drawing
pdf
Plan Dim.
dwg
Heat rejection at the following conditions: Tin: 35,0ºC Tout 30,0ºC Twb: 24,0ºC
COMPLETE (WITH BASIN AND LOUVERS) (A)
EWK 2100 3372,6 5100 19100 22 4740 4610 6750 seleccionar seleccionar
EWK 3100 5117,1 6800 24800 30 7040 4610 7095 seleccionar seleccionar
EWK 4500 7267.5 10100 36400 37 7040 6900 7255 seleccionar seleccionar
EWK 4200 6745,2 10300 34700 2×22 4740 9240 7050 seleccionar seleccionar
EWK 6200 10234,2 13800 49800 2×30 7040 9240 7395 seleccionar seleccionar
EWK 9000 14535,0 20400 72900 2×37 7040 13850 7555 seleccionar seleccionar
NO BASIN (B)
EWK 2100 3372,6 4200 5900 22 4740 4610 6150 seleccionar seleccionar
EWK 3100 5117,1 5600 8100 30 7040 4610 6655 seleccionar seleccionar
EWK 4500 7267.5 8300 12100 37 7040 6915 6495 seleccionar seleccionar
EWK 4200 6745,2 8500 11900 2×22 4740 9240 6450 seleccionar seleccionar
EWK 6200 10234,2 11400 16400 2×30 7040 9240 6955 seleccionar seleccionar
EWK 9000 14535,0 16800 24300 2×37 7040 13850 6795 seleccionar seleccionar
NO BASIN / NO LOUVERS (C)
EWK 2100 3372,6 3300 5000 22 4740 4610 4175 seleccionar seleccionar
EWK 3100 5117,1 4400 6900 30 7040 4610 4520 seleccionar seleccionar
EWK 4500 7267.5 6500 10300 37 7040 6915 4680 seleccionar seleccionar
EWK 4200 6745,2 6700 10100 2×22 4740 9240 4175 seleccionar seleccionar
EWK 6200 10234,2 9000 14000 2×30 7040 9240 4520 seleccionar seleccionar
EWK 9000 14535,0 13200 20700 2×37 7040 13850 4680 seleccionar seleccionar

Working Principles

Cooling towers bring a cold and dry air mass in counter-flow to hot water that comes from an industrial or air conditioning process. Part of this water evaporates, cooling the rest. The necessary heat for this is approx.597 Kcal/litre. The cold water produced is returned into the process to re-iniciate the cycle. The equipment with this evaporative refrigeration principle are very important for energy efficiency.

The difference between the required cold water temperature and the wet bulb temperature (called cooling limit distance), is significant to determine the size of the tower. The smaller the cooling distance is, the bigger the interchanging surface is needed. The limit distance must be of at least 3-4º C. In open cooling towers there is a close contact water-air, which is bigger thanks to the fill packings, that provide a big surface of exchange, improving performance and evaporation. There are different kinds of fill packing for different water quality.

Additional equipment

  • PRFV with SANIPACKING® treatment casing
  • Access ladder & Hand rail to the fan motor
  • Access door in Polypropylene
  • Vibration switch for ventilation equipment
  • Electric motor frequency converters
  • PTC sensor for the motor
  • Exhaust silencer
  • Low noise fan
  • Sensors for the level of water in the basin
  • Winter pack (Thermostat & Immersion heater) to protect from low temperatures
  • Attenuators of noise from the drops in the basin
  • SMART Cooling Tower